modbusua Gateway is a cross‑platform (Windows, Linux) I/O server that bridges data
between the Modbus protocol and OPC UA (Open Platform Communications Unified Architecture).
It is implemented in C++ as an open‑source server and can run as a console application
or a background service/daemon.
The gateway collects data from existing industrial PLCs or other Modbus devices (industrial sensors, meters, etc.) via Modbus, processes it, and exposes it through the widely adopted OPC UA protocol.
The project is built on two open‑source libraries:
- Modbus (client side): https://github.com/serhmarch/ModbusLib
- OPC UA (server side): https://github.com/open62541/open62541
Address Space Example:
- Modern C++ implementation (C++17 and above)
- Cross‑platform support (Windows, Linux)
- Configuration via a plain CONF/INI file
- Logging to file with rotation and to the OS system log (Windows/Linux)
- Runs as a console app or Windows service/Linux daemon
- Multithreaded architecture for performance
- Modular design for easy extensibility
- Built‑in OPC UA server with configurable address space
- Modbus TCP/RTU/ASCII support for a wide range of devices
- Connection parameters, timeouts, retries configurable via the config file
- Hot configuration reload without stopping the server
- Support for common data types (bits, integers, floating‑point)
- Scalable to many devices and tags
- Built‑in diagnostics and monitoring of server and connections
- Robust error handling and reconnection logic
- Easy integration with existing SCADA systems and other upper‑level software
+--------------------+ Modbus +------------------+ OPC UA +-----------------+
| PLC/Device | <-------------> | modbusua Gateway | <----------> | SCADA Client |
| | | | | |
| - Modbus registers | | - Modbus client | | - Data ingest |
| | | - OPC UA server | | - Archiving |
| | | | | - Visualization |
| | | | | |
+--------------------+ +------------------+ +-----------------+
- CMake 3.20 or newer
- C++17 compliant compiler
- Git to clone the repository
git clone --recursive https://github.com/serhmarch/modbusua.git
cd modbusua
mkdir build && cd build
cmake .. -DCMAKE_BUILD_TYPE=Release
cmake --build . --config Releasegit clone --recursive https://github.com/serhmarch/modbusua.git
cd modbusua
mkdir build && cd build
cmake .. -DCMAKE_BUILD_TYPE=Release
cmake --build . --config ReleaseNext cmake --install commands are identical:
cd <build_directory>
cmake --install .
cmake --install . --prefix "C:\Program Files\modbusua"Build directory is where cmake_install.cmake is located.
:: Install as a service (requires Administrator)
modbusuaservice.bat -i -n modbusuaService
:: Uninstall the service
modbusuaservice.bat -u -n modbusuaServiceBuild an MSI installer using the WiX Toolset:
cd install/windows
cmake --build . --target modbusua-msiNext cmake --install commands are identical:
cd <build_directory>
cmake --install .
cmake --install . --prefix /Build directory is where cmake_install.cmake is located.
Next example shows how to install and enable the modbusua service manually:
# Copy files
sudo cp modbusua /usr/bin/
sudo cp modbusua.conf /etc/modbusua/
sudo cp modbusua.service /etc/systemd/system/
# Enable the service
sudo systemctl enable modbusua
sudo systemctl start modbusua
# Check status
sudo systemctl status modbusuaBuild DEB/RPM packages:
# Build a DEB package
cmake --build . --target modbusua-deb
# Build an RPM package
cmake --build . --target modbusua-rpmInstall the generated .deb package:
sudo dpkg -i modbusua-0.4.0_amd64.deb
# or
sudo apt install ./modbusua-0.4.0_amd64.debRemove previously installed modbusua package:
sudo dpkg -r modbusua # remove package (but not conffiles)
sudo dpkg -P modbusua # remove everything (even conffiles)
# or
sudo apt remove modbusuaInstall the generated .rpm package:
sudo rpm -i modbusua-0.4.0_amd64.rpm
# or
sudo dnf install ./modbusua-0.4.0_amd64.rpmRemove previously installed modbusua package:
sudo rpm -e modbusua # remove package (but not conffiles)
sudo rpm -e --noscripts modbusua # remove everything (even conffiles)
# or
sudo dnf remove modbusuaAdd modbusua to the autostart and immediately run:
sudo systemctl enable --now modbusuaConfiguration is done via the modbusua.conf file. Main configuration objects:
[Port]
Type=TCP
Host=192.168.1.100
Port=502
Timeout=5000[Device]
Port=Port1
Unit=1[Log]
Log.flags=Error|Warning|Info
Log.file.path=modbusua.log
Log.file.maxsize=10MB| Option | Short | Parameter | Description |
|---|---|---|---|
| --version | -v | - | Show program version |
| --help | -? | - | Show help |
| --file | -f | Configuration file (default: modbusua.conf) |
# modbusua.conf
[System]
Name=modbusua Gateway
Description=OPC UA to Modbus Gateway
[Port.MainPort]
Name=MainPort
Type=TCP
Host=192.168.1.10
Port=502
Timeout=3000
[Device.Station1]
PortName=MainPort
Name=PLC1
ModbusUnit=1
[OpcUa]
Port=4840# Run with a configuration file
./modbusua -f /etc/modbusua/modbusua.conf
# Check connectivity
tail -f /var/log/modbusua.log| Category | Purpose |
|---|---|
| Error | Critical failures that may cause stoppage or incorrect operation |
| Warning | Non‑critical issues that do not stop the program |
| Info | General diagnostic messages |
| Trace | Detailed diagnostic messages |
| TraceDetails | Extra‑detailed diagnostic messages |
| CtorDtor | Creation/destruction of key program components |
| EntryExit | Entry/exit of major functions |
| ThreadStartStop | Start/stop of system threads |
| Connection | Connect/disconnect events to remote objects over the network |
| Item | Creation/execution of individual ItemReference variables |
| Message | Creation/execution of message objects (packets) |
| Protocol | Modbus‑specific protocol messages |
| Receive | Incoming Modbus network frames |
| Send | Outgoing Modbus network frames |
# Linux - systemd logs
journalctl -u modbusua -f
# Windows - Event Viewer
# Applications and Services Logs → modbusua
# Log file
tail -f modbusua.log | grep Errormodbusua/
├── src/ # Source code
│ ├── core/ # Common classes: string, variant, thread, etc.
│ ├── ua/ # OPC UA server
│ └── device/ # Modbus devices
├── install/ # Installation scripts
│ ├── windows/ # WiX MSI installer
│ └── linux/ # DEB/RPM packages
├── doc/ # Documentation
├── examples/ # Configuration examples
└── tests/ # Unit tests
# Run tests
cmake --build . --target test
ctest --output-on-failure
# Code coverage (enable tests)
cmake .. -DCMAKE_BUILD_TYPE=Debug -DCN_TESTS_ENABLED=ONThis project is licensed under the MIT License.
MIT License
Copyright (c) 2025 serhmarch
Permission is hereby granted, free of charge, to any person obtaining a copy
of this software and associated documentation files (the "Software"), to deal
in the Software without restriction, including without limitation the rights
to use, copy, modify, merge, publish, distribute, sublicense, and/or sell
copies of the Software...
- Source code: https://github.com/serhmarch/modbusua
- Documentation: doc/pages/
- Issue tracking: https://github.com/serhmarch/modbusua/issues
- Modbus library: https://github.com/serhmarch/ModbusLib
- OPC UA library: https://github.com/open62541/open62541
- OPC UA standard: https://opcfoundation.org/
serhmarch — development and project support.
Homepage: https://github.com/serhmarch
modbusua Gateway — OPC UA to Modbus Gateway